Yaskawa iQpump1000

45 feilkoder dokumentert

ACCUM

Accumulated Level Fault

The total volume of water flow measured over time by the flow meter has exceeded the fault level setting. This fault is effective when P6-15 (Accumulated Behavior) is set to 2 (fault with manual monitor reset) or 3 (fault with automatic monitor reset).

AJF

Anti-Jam Fault

The drive was not able to clear debris from the impeller in fewer than the number of attempts set in P7-02. This fault is effective only when P7-01 (Anti-jam Operation) is set to 1 (enabled).

AUXFB

PI Aux Lvl Loss (Wire-break detection for PI Aux Feedback Level)

The analog input programmed for “PI Aux FB Level” (H3-oo = 27) has dropped below 3 mA or risen above 21 mA for longer than 1 second.

CPF26-CPF35, CPF40-CPF43

Control Circuit Error / CPU error

These codes indicate a general control circuit or CPU error within the drive, suggesting internal hardware damage. This critical fault can affect the drive's core functionality and may necessitate replacement of components.

DIFF

Differential Feedback Detected

This fault (or minor fault/alarm) occurs when the difference between the PID Feedback and the Differential Feedback (monitor H3-OO = 28) exceeds the level set in parameter P4-18 for the duration specified in P4-19. It indicates an inconsistency in the feedback signals used for PID control.

E5

SI-T3 Watchdog Timer Error

The SI-T3 watchdog timer has timed out, indicating that data has not been received from the PLC. This often points to a communication issue with the PLC.

EF

Forward/Reverse Run Command Input Error

Both forward run and reverse run commands have been received simultaneously and maintained for longer than 0.5 seconds. This is a sequence error that causes the motor to ramp to a stop, indicating conflicting commands from the control system.

EF0

Option Card External Fault

An external fault condition is present, received from the PLC via an option card. Depending on parameter F6-03, this condition may either stop the drive (F6-03 ≠ 3, page 254) or allow it to continue running as a minor fault (F6-03 = 3, page 273). This indicates an external issue communicated to the drive.

EF1

Pump Fault (Input Terminal S1)

An external fault has been triggered at multi-function input terminal S1 by an external device. This condition is signaled to the drive, potentially as a minor fault or a full fault depending on drive configuration.

EF2

Pump Fault (Input Terminal S2)

An external fault has been triggered at multi-function input terminal S2 by an external device. This condition is signaled to the drive, potentially as a minor fault or a full fault depending on drive configuration.

EF3

Pump Fault (Input Terminal S3)

An external fault has been triggered at multi-function input terminal S3 by an external device. This condition is signaled to the drive, potentially as a minor fault or a full fault depending on drive configuration.

EF4

Pump Fault (Input Terminal S4)

An external fault has been triggered at multi-function input terminal S4 by an external device. This condition is signaled to the drive, potentially as a minor fault or a full fault depending on drive configuration.

EF5

Pump Fault (Input Terminal S5)

An external fault has been triggered at multi-function input terminal S5 by an external device. This condition is signaled to the drive, potentially as a minor fault or a full fault depending on drive configuration.

EF6

Pump Fault (Input Terminal S6)

An external fault has been triggered at multi-function input terminal S6 by an external device. This condition is signaled to the drive, potentially as a minor fault or a full fault depending on drive configuration.

EF7

Pump Fault (Input Terminal S7)

An external fault has been triggered at multi-function input terminal S7 by an external device. This condition is signaled to the drive, potentially as a minor fault or a full fault depending on drive configuration.

EF8

Pump Fault (Input Terminal S8)

An external fault has been triggered at multi-function input terminal S8 by an external device. This condition is signaled to the drive, potentially as a minor fault or a full fault depending on drive configuration.

EoF

Emergency Override Forward Run

The multi-function digital input for Emergency Override Forward (H1-oo = AF) has been closed, indicating an active emergency override condition for forward operation.

Eor

Emergency Override Reverse Run

The multi-function digital input for Emergency Override Reverse (H1-oo = B0) has been closed, indicating an active emergency override condition for reverse operation.

Err

EEPROM Write Error

Data cannot be written to the EEPROM, possibly due to noise corruption during writing or a hardware problem. This indicates an issue with the drive's internal non-volatile memory.

FAn

Internal Fan Error

This fault indicates a malfunction of the internal cooling fan or a failure of the magnetic contactor to the power supply. It can be triggered if the fan has exceeded its expected performance life or is otherwise damaged.

FDBKL

PID Feedback Loss (Wire Break)

The analog input programmed for PID feedback has risen above 21 mA or fallen below 3 mA, indicating a loss or out-of-range signal. This fault is effective only when b5-12 (Feedback Loss 4 to 20 mA Detection Selection) is set to 2 (fault).

FbH

PID Feedback Loss (High)

The analog input programmed for PID feedback has risen above 21 mA. This occurs when the PI feedback source is incorrectly installed, not working, or has a wiring issue. The drive's response to this condition is controlled by parameters b5-12 and b5-13.

FbL

PID Feedback Loss (Low)

The analog input programmed for PID feedback has fallen below 3 mA. This occurs when the PI feedback source is incorrectly installed, not working, or has a wiring issue (wire break). The drive's response to this condition is controlled by parameters b5-12 and b5-13.

Flow Rate Limit

Flow Rate Limit

The drive output speed is being limited due to the Flow Rate (U1-83). This condition indicates that the system flow is either excessively high or low, triggering the internal limiter.

GF

Ground Fault

A current short to ground exceeding 50% of rated current has been detected on the output side of the drive. This fault is enabled when L8-09 is set to 1. Persistent ground faults can indicate severe motor or cable damage.

HFB

High Feedback

The feedback signal has risen above the level set in P1-11 (High Feedback Level) for the time set in P1-12 (High Feedback Level Fault Delay Time). This fault is effective only when P1-13 (High Feedback Selection) is set to 0 (Fault and digital output).

HIAUX

High PI Auxiliary Feedback Level

The PI Aux Feedback has risen above the Q6-12 level for longer than the time set in Q6-13, while the drive is running in AUTO mode with output frequency greater than zero. This indicates an abnormally high auxiliary feedback signal.

HIFLO

High Flow

The measured water flow has risen above the P6-17 level for the time set in P6-18. This fault is effective only when P6-19 (High Flow Select) is set to 2 (fault). This indicates an excessively high flow condition.

HISUC

High Suction Pressure

The suction pressure has risen above the level set in Q5-12 for longer than the time set in Q5-13. This fault is effective only when Q5-14 (High Suction Pressure Behavior Select) is set to 2 (fault).

HWL

High Water Level

The digital input configured for “High Water Level” (H1-oo = 90) is active. This fault indicates that the physical water level is high, or parameter P1-31 (High Water Digital Input Configuration) is programmed incorrectly.

LOP

Loss of Prime

The pump load (based on P1-18) dropped below P1-19 for P1-20 time, and output frequency rose above P1-21. This fault is effective when P1-22 (Loss of Prime Selection) is set to 0 (fault).

LOSUC

Low Suction Pressure

The suction pressure has fallen below the level set in Q5-09 for longer than the time set in Q5-10. This fault is effective only when Q5-11 (Low Suction Pressure Behavior Select) is set to 2 (fault).

LOWFL

Low Flow

After the P6-08 delay at start, the measured water flow has fallen below the P6-06 level for the time set in P6-07. This fault is effective only when P1-09 (Low Flow Select) is set to 2 (fault).

LOWWL

Low Water Level

The water level has fallen below the level set in Q4-09 for longer than the time set in Q4-10. This fault is effective only when Q4-11 (Low Level Behavior) is set to 2 (fault).

LWL

Low Water Level (Digital Input)

The digital input configured for “Low Water Level” (H1-oo = 8F) is active. This fault indicates that the physical water level is low, the switch is faulty, or the input parameter P1-30 is incorrectly configured.

MSL

Net Master Lost

The MEMOBUS master has been lost, meaning no message has been received from the master within the time set in P9-26. This fault occurs when P9-27 (Network Recovery) is set to 3 (Fault MSL).

Uv3

Undervoltage 3 (Soft-Charge Bypass Circuit Fault)

The soft-charge bypass circuit has failed. This could be due to damage to the relay or contactor within the circuit, or the circuit exceeding its expected performance life as indicated by monitor U4-06.

Uv4

Gate Drive Board Undervoltage

A voltage drop has occurred in the gate drive board circuit, indicating insufficient power supply to the gate drive board. This fault is specifically detected in models 4A0930 and 4A1200.

VLTS

Volute-Thermostat Fault

This fault occurs when a digital input assigned to the volute/thermostat input (H1-0o = 88 or 89) is active, or if both volute/thermostat inputs are programmed simultaneously. Auto-restart is controlled by parameter L5-53.

WLL

Water Level Loss

An analog input programmed for setting 23 'WaterLvl/Suction' has dropped below 3 mA or risen above 21 mA for longer than 1 second. This indicates a problem with the level sensor or its wiring.

bAT

Digital Operator Battery Voltage Low

The digital operator's internal battery is low and needs replacement. This fault indicates that the operator may lose settings or functionality if the battery is not replaced.

bUS

Option Communication Error

The connection was lost after establishing initial communication with an option card, or no signal was received from the PLC. This fault is only detected when the run command frequency reference is assigned to an option card.

boL

Braking Transistor Overload Fault

The braking transistor reached its overload level, indicating excessive regenerated energy. This typically occurs due to an incorrect or undersized braking resistor, or aggressive deceleration settings.

dnE

Drive Disabled

The drive is disabled because the 'Drive Enable' function is configured to a multi-function contact input (parameter H1-OO = 6A), and this contact is currently open. This prevents the drive from operating, potentially indicating an improper control sequence.

voF

Output Voltage Detection Fault

A problem is detected with the voltage on the output side of the drive. This indicates damaged hardware, specifically an internal drive module MC / FAN overheat protection circuit board due to abnormal ambient operating power or temperature.