Hva betyr dnE ?

The drive is disabled because the 'Drive Enable' function is configured to a multi-function contact input (parameter H1-OO = 6A), and this contact is currently open. This prevents the drive from operating, potentially indicating an improper control sequence.

Vanlige årsaker

  • The multi-function contact input configured for Drive Enable (H1-OO = 6A) is open
  • Improper operation sequence of the Drive Enable command from the control system

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the physical state of the multi-function contact input configured as Drive Enable (parameter H1-OO = 6A).

  2. 2

    Ensure the Drive Enable contact input is closed to enable drive operation.

  3. 3

    Review the overall control system operation sequence to confirm correct timing and logic for the Drive Enable command.