HFB

High Feedback

Yaskawa · iQpump1000

Hva betyr HFB ?

The feedback signal has risen above the level set in P1-11 (High Feedback Level) for the time set in P1-12 (High Feedback Level Fault Delay Time). This fault is effective only when P1-13 (High Feedback Selection) is set to 0 (Fault and digital output).

Vanlige årsaker

  • Feedback signal has risen above the threshold P1-11 for longer than the delay time P1-12.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Set the High Feedback fault characteristics using parameters P1-11 and P1-12.

  2. 2

    Control drive response to this condition using P1-13 (High Feedback Selection).

  3. 3

    Control auto-restart of this fault using L5-41 (High Feedback Fault Retry Selection).