WLL
Water Level Loss
Yaskawa · iQpump1000
Hva betyr WLL ?
An analog input programmed for setting 23 'WaterLvl/Suction' has dropped below 3 mA or risen above 21 mA for longer than 1 second. This indicates a problem with the level sensor or its wiring.
Vanlige årsaker
- Level sensor malfunction or damage
- Wiring fault to the level sensor
- Analog input signal outside the 3-21 mA range
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Repair or replace the level sensor
- 2
Check wiring between the level sensor and the drive