EF
Forward/Reverse Run Command Input Error
Yaskawa · iQpump1000
Hva betyr EF ?
Both forward run and reverse run commands have been received simultaneously and maintained for longer than 0.5 seconds. This is a sequence error that causes the motor to ramp to a stop, indicating conflicting commands from the control system.
Vanlige årsaker
- Simultaneous activation of both forward and reverse run commands for more than 0.5 seconds
- Improper control sequence for run commands from the PLC or control system
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Review the control sequence for forward and reverse run commands from the PLC or control system.
- 2
Verify that simultaneous activation of both forward and reverse commands for more than 0.5 seconds is prevented by control logic or wiring.
- 3
Correct any identified sequence errors in the control program or wiring to ensure only one run command is active at a time.