LOSUC
Low Suction Pressure
Yaskawa · iQpump1000
Hva betyr LOSUC ?
The suction pressure has fallen below the level set in Q5-09 for longer than the time set in Q5-10. This fault is effective only when Q5-11 (Low Suction Pressure Behavior Select) is set to 2 (fault).
Vanlige årsaker
- System suction pressure has fallen below the configured threshold.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Increase the system pressure.
- 2
Set the Low Suction fault characteristics using parameters Q5-09, Q5-10, and Q5-18.
- 3
Control drive response to this condition using Q5-11 (Low Suction Pressure Behavior Select).
- 4
Control auto-restart of this fault using Q5-11 (Low Suction Pressure Behavior Select) and Q5-15 (Suction Pressure Auto-restart Time).