Oversetter...
FbH
PID Feedback Loss (High)
Yaskawa · iQpump1000
Hva betyr FbH ?
The analog input programmed for PID feedback has risen above 21 mA. This occurs when the PI feedback source is incorrectly installed, not working, or has a wiring issue. The drive's response to this condition is controlled by parameters b5-12 and b5-13.
Vanlige årsaker
- PI feedback source is incorrectly installed or not working
- Analog input programmed for PID feedback has risen above 21 mA
- Wiring issue in the PID feedback circuit
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Confirm that the PID feedback source is installed and working properly
- 2
Verify the analog input signal for PID feedback is within the expected 3-21 mA range
- 3
Check drive parameters b5-12 (Feedback Loss 4 to 20 mA Detection Selection) and b5-13 (Feedback Loss Go To Frequency) for drive response settings
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Yaskawa iQpump1000