Yaskawa E7 Drive

85 fault codes documented

3021

Speed Search Retry Error

The speed search function has attempted to retry more times than allowed by the b3-19 parameter. This typically indicates that the speed search settings in b3-17 and b3-18 are not correctly configured for the application, preventing successful speed identification within the set limits.

BUS

Option Communication Error

After initial communication was established, the connection to the option board was lost. This indicates a broken connection or the master device has stopped communicating, leading to loss of control or monitoring through the option card.

BUS Option Com Err

Option Communication Error

After initial communication was established, the connection to the option board was lost. This indicates a broken connection or that the master controller stopped communicating, preventing data exchange.

CALL

SI-F/G ComCall

A serial communication transmission error has occurred, indicating that communication has not yet been established. This is typically due to improper connections or user software not configured to the correct baud rate or communication settings, preventing data exchange.

CE

Modbus Communication Error

Control data was not received correctly for two seconds over the Modbus connection. This implies a broken Modbus connection or the master device has stopped communicating, preventing proper control and data exchange.

CE Memobus Com Err

Modbus Communication Error

Control data was not received correctly for two seconds, indicating a breakdown in Modbus communication. This fault occurs when H5-05=1 and H5-04=0 to 2, typically due to a broken connection or the master stopping communication.

CF Out of Control

Control Fault

A torque limit was continuously reached for 3 seconds or longer during a ramp to stop while operating in open-loop vector control. This fault typically indicates that the motor parameters are not correctly set, preventing the drive from controlling torque effectively.

CPF00

Operator Communication Fault

Transmission between the Drive and the Digital Operator was not established within 5 seconds after supplying power. This indicates a potential issue with the Digital Operator cable, the operator unit itself, or a faulty control board within the Drive.

CPF01

Operator Communication Fault 2

After communication started with the digital operator, a communication fault occurred for 2 seconds or more. This indicates a problem with the digital operator cable, the operator unit, or the control board, leading to intermittent or lost local control.

CPF02

Baseblock Circuit Fault

A baseblock circuit fault was detected at power-up, indicating a gate array hardware failure within the drive during its startup sequence. This is a critical internal drive component failure, rendering the drive inoperable.

CPF03

EEPROM Fault

An EEPROM fault was detected, meaning the checksum is not valid, potentially due to noise or spikes on the control circuit input terminals. This critical memory fault can lead to incorrect parameter storage or drive operation.

CPF04

CPU Internal A/D Converter Fault

A fault in the CPU's internal Analog-to-Digital converter was detected. This issue typically results from noise or electrical spikes on the control circuit input terminals, impairing the CPU's ability to accurately process internal analog signals.

CPF05

CPU External A/D Converter Fault

A fault in the CPU's external A/D converter was detected, often caused by noise or spikes on the control circuit input terminals. This affects the drive's ability to accurately read external analog signals, potentially leading to incorrect control or protection responses.

CPF5

CPU A/D Converter Fault

A CPF5 fault indicates a critical internal issue with the drive's CPU Analog-to-Digital (A/D) converter. This is a hardware malfunction within the drive's control board, meaning the drive cannot accurately measure and process internal signals. If this fault occurs, the drive is unable to function correctly and requires internal repair or replacement.

CPF06

Option Board Connection Error

The option board was not connected properly or has been damaged, indicating a problem with its physical integrity or functionality. This fault can also suggest damage to the Drive itself affecting the option board interface.

CPF07

ASIC Internal RAM Fault

Control circuit failure or damage, specifically within the ASIC's internal RAM. This is a critical internal hardware fault indicating a memory integrity issue that can lead to unpredictable Drive behavior.

CPF08

Watchdog Timer Fault

A Watchdog Timer Fault was detected, indicating an issue with the drive's internal timing and supervision mechanism. This is a critical internal hardware failure, suggesting control circuit damage and leading to drive malfunction or shutdown.

CPF09

CPU-ASIC Mutual Diagnosis Fault

Control circuit failure or damage involving a mutual diagnosis fault between the CPU and ASIC. This is a critical internal hardware fault affecting the core processing units and indicates a severe internal malfunction.

CPF10

ASIC Version Fault

An ASIC Version Fault was detected, indicating an issue with the ASIC's version identification or integrity. This points to control circuit damage, compromising the drive's fundamental operation.

CPF20

Option Card Fault

This fault can be caused by an option card connector connection fault or an option card A/D converter fault. It indicates an issue with the option board's hardware or its connection, preventing proper functionality and communication.

CPF21

Self-diagnosis Fault of Option Board

A self-diagnosis fault was detected on the option board, potentially due to noise or spikes on the communication line or a defective option board itself. This indicates an internal issue with the option board's CPU, impacting its operation.

CPF22

Communication Option Card Code Number Fault

An unrecognizable option board is connected to the control board, indicating a type mismatch or an unsupported option card. This prevents the drive from correctly interfacing with the option card, leading to functional limitations or failure.

CPF23

Option DPRAM Err

An option board is not correctly connected to the control board or an option board that is not made for the Drive is attached. This indicates a physical connection issue or hardware mismatch, risking improper communication or drive malfunction.

DEV

Excessive Speed Deviation

This fault occurs in Flux Vector control (A1-02=3) when the actual motor speed deviates from the reference speed by more than the F1-10 setting for longer than the F1-11 time. It often indicates a locked load or an inability for the motor to follow its command. Unresolved, this can lead to poor process control, mechanical stress on the system, or motor overheating due to sustained effort.

E-15

SI-F/G Communication Error Detected

A communication error has occurred when the SI-F/G Option Card is designated as the source for run commands or frequency reference (b1-01=3 and/or b1-02=3), and communication with it is lost. This implies a failure in the communication link or configuration with the SI-F/G card. Without proper communication, the Drive cannot receive critical commands or references, leading to a stop.

E5

SI-T Watchdog Error

This fault indicates a consistency error in received control data or a synchronization problem between the master controller and the Drive when using an SI-T option card. It signifies a breakdown in reliable communication, which can lead to unpredictable Drive behavior or complete loss of control. Such errors require immediate attention to restore stable operation.

EF

External Fault (Simultaneous Fwd/Rev Command)

Both the forward and reverse run commands were input simultaneously for 500ms or more, causing the motor to stop. This is an external sequencing logic error, which could lead to motor damage or unsafe operation if not corrected.

EF0

Opt External Flt

An external fault condition exists, originating from the communication option card. This suggests an issue with an external device or signal connected via the option card, potentially leading to incorrect drive operation. This can also appear as a flashing alarm.

EF3

Ext Fault S3

An external fault condition exists connected to a multi-function digital input terminal S3. This implies an issue with an external device or wiring connected to this specific input, which could stop the drive or cause unintended behavior. This can also appear as a flashing alarm.

EF4

Ext Fault S4

An external fault condition exists connected to a multi-function digital input terminal S4. This implies an issue with an external device or wiring connected to this specific input, which could stop the drive or cause unintended behavior. This can also appear as a flashing alarm.

EF5

External Fault at Terminal S5

This fault is triggered when an external condition connected to multi-function digital input terminal S5 activates the Drive's external fault function, causing the Drive to stop. It indicates an issue with the external device or process monitored by S5, which could lead to machine downtime or safety risks if misidentified.

EF6

Ext Fault S6

An external fault condition exists connected to a multi-function digital input terminal S6. This implies an issue with an external device or wiring connected to this specific input, which could stop the drive or cause unintended behavior. This can also appear as a flashing alarm.

EF7

External Fault at Terminal S7

This fault is triggered when an external condition connected to multi-function digital input terminal S7 activates the Drive's external fault function, causing the Drive to stop. It indicates an issue with the external device or process monitored by S7, which could lead to machine downtime or safety risks if misidentified.

EF8

External Fault at Terminal S8

This fault is triggered when an external condition connected to multi-function digital input terminal S8 activates the Drive's external fault function, causing the Drive to stop. It indicates an issue with the external device or process monitored by S8, which could lead to machine downtime or safety risks if misidentified.

End - 3

Auto-tuning Data Invalid

The rated current set value is set too high, or there's an excessive V/F set value, or a motor iron core saturation coefficient fault, causing the auto-tuning results to be invalid. This is an alarm that indicates incorrect motor or drive parameter settings post-tuning, which could lead to suboptimal performance or protection issues.

Er - 01

Motor Data Fault

This auto-tuning fault indicates an error in the motor data input, a mismatch between motor output and rated current, or an issue with no-load current vs. input motor rated current during vector control auto-tuning. Incorrect motor data prevents the Drive from accurately characterizing the motor, potentially leading to inefficient operation or damage from improper control.

Er - 02

Auto-tuning Minor Fault

A minor fault was detected during the auto-tuning process. This could indicate slight discrepancies in input data, wiring issues, or problems with the mechanical load connected to the motor, impacting the accuracy of tuning.

Er - 03

Auto-tuning Interrupted

The auto-tuning process was interrupted because the STOP key was pressed during its operation. This is a user-initiated stop, not an actual system fault, and prevents the tuning from completing.

Er - 04

Auto-tuning Resistance Fault

Auto-tuning did not complete within the specified time, or the tuning result for resistance fell outside the parameter set range. This can be caused by incorrect input data, motor wiring issues, or a connected mechanical load interfering with the tuning.

Er - 05

No-Load Current Fault

During Auto-Tuning, this fault signifies that the process did not complete within the specified time or the measured no-load current was outside the expected range. This can be caused by incorrect motor data, wiring issues, or a connected load influencing the no-load measurement. An incorrect no-load current value will lead to suboptimal motor parameterization and control.

Er - 08

Rated Slip Fault

This Auto-Tuning fault means the process did not complete within the specified time, or the calculated rated slip value was outside the parameter setting range. It can also occur if the motor rated voltage setting (T1-03) is higher than the Drive's actual input voltage. Incorrect slip data will negatively impact motor speed regulation and torque control.

Er - 09

Auto-tuning Acceleration Fault

The motor did not accelerate as specified during the auto-tuning process. This may be due to an acceleration time setting that is too short, torque limits set too low, or the motor being connected to a heavy mechanical load.

Er - 11

Motor Speed Fault

Detected during rotational Auto-Tuning in vector control (A1-02=2 or 3), this fault indicates that the torque reference exceeded 100% during acceleration. This typically points to an issue with acceleration time, incorrect PG (encoder) pulse data, or an excessive mechanical load on the motor. Exceeding torque limits during tuning will lead to inaccurate motor parameterization and potentially inefficient operation.

Er - 12

Current Detection Circuit Fault

The current flow exceeded the motor rated current, the current detection value symbol was reversed, or there is an open-phase condition on any of the U/T1, V/T2, and W/T3 output terminals. This indicates a severe issue with the motor wiring or the drive's internal current detection, risking motor or drive damage.

Er - 13

Leakage Inductance Fault

Auto-tuning did not finish within the set time, or the tuning result for leakage inductance fell outside the parameter setting range. This typically points to issues with motor wiring, preventing the drive from accurately determining motor inductance.

ERR

EEPROM Read/Write Error

This fault occurs when data written to the EEPROM does not match, often due to power supply being turned OFF unexpectedly or repeated parameter resets. It indicates potential internal data corruption that can prevent proper operation.

F6-CEA

Option PCB Communication Error Alarm

This alarm occurs when a serial communication option board, attached to the drive at the 2CN connector, detects a communication error, and parameter F6-01 is specifically set to '3: Alarm Only'. In this state, the drive acknowledges the communication issue without energizing the fault output or stopping operation, allowing for continuous monitoring despite communication problems.

F6-CEF

Option PCB Communication Error Fault

This fault occurs when a serial communication option board, attached to the drive at the 2CN connector, detects a communication error. Unless parameter F6-01 is specifically set to '3: Alarm Only', this condition will energize the fault output and potentially stop the drive, indicating a critical problem with the communication link to the option board.

FAN

Drive’s Cooling Fan Fault

A fault with the Drive's internal cooling fan has been detected, leading to the activation of Drive overload protection due to excessive internal thermal value. This typically occurs when the fan stops running and the Drive continues operating under load, causing heat to build up. Unresolved, this will lead to repeated overheating faults and potential damage to the Drive's power components.

FBL

PI Feedback Loss

This fault occurs when PI Feedback Loss Detection is programmed to fault (b5-12 = 2) and the PI Feedback is below the PI Feedback Loss Detection Level (b5-13) for the PI Feedback Loss Detection Time (b5-14). The PI Feedback source (e.g., transducer, sensor, building automation signal) is not installed correctly or is not working, risking unstable control.

GF

Ground Fault

The Drive output grounding current has exceeded 50% of the Drive's rated output current. This indicates a motor lead shorted to ground or a defective DCCT (Direct Current Current Transformer), posing risks of electrical shock, equipment damage, or fire.

LF

Output Open-Phase

An open-phase condition has been detected at the Drive's output, where the output current imbalance exceeds 5% (L8-07=1 enabled). This is commonly caused by a broken wire in the motor cable, a broken winding in the motor, or loose output terminal connections. Operating with an open phase can cause motor damage due to imbalanced currents and vibrations, as well as reduced performance.

OC

Overcurrent Fault

This fault indicates an excessive current draw, which can lead to motor and drive damage if not promptly addressed. It can occur during momentary power loss recovery, DC Injection Braking, or during acceleration if the mechanical load is too large or the acceleration time is set too short. The drive will trip and stop operation upon detection of this fault.

OH

Heatsink Overheat

The temperature of the Drive's heatsink has exceeded the programmed setpoint (L8-02, L8-03=0 to 2), indicating inadequate cooling or excessive ambient temperature. This can be caused by a nearby heat source, dirt buildup on fans/heatsink, or high room temperature. Persistent overheating will lead to nuisance trips, reduced performance, and can significantly shorten the Drive's lifespan.

OH1

Fan Failure Overheat 1

An OH1 fault signals an overheat condition specifically caused by the failure or malfunction of the drive's internal cooling fan. When L8-32 is enabled, this fault will occur, indicating that the drive's ability to dissipate heat is compromised. Prolonged operation without adequate cooling will inevitably lead to damage of internal power components and system shutdown.

OH2

Heatsink Overtemperature

An OH2 fault occurs when any of the heatsink thermistors measure a temperature exceeding the level set in L8-02. This indicates that the drive's heatsink is overheating, typically due to insufficient cooling, excessive ambient temperature, or prolonged overload on the drive. Sustained high temperatures can severely degrade the lifespan of the drive's power components and lead to premature failure.

OH3

Motor Overheat Alarm (Level 3)

This alarm indicates that the motor's temperature, as monitored by an analog input (H3-09=E), has exceeded the OH3 alarm threshold (1.17V). It serves as an early warning of potential motor overheating, allowing for intervention before a more critical fault occurs that could lead to a drive stop.

OH4

Motor Overheat Fault (Level 4)

The OH4 fault indicates a critical over-temperature condition in the motor, detected when the motor temperature analog input (H3-09=E) surpasses the 2.34V fault level. Upon activation, the drive will immediately stop the motor using a configured method to prevent damage. Operating a motor under this severe overheat condition risks immediate insulation breakdown, permanent motor failure, and safety issues.

OL1

Motor Thermal Overload Fault

The OL1 fault is triggered when the motor connected to the drive experiences prolonged overcurrent, causing it to exceed its thermal capacity. This protection is configured by parameters like L1-01 (protection selection) and L1-02 (overload time constant). Continuing to operate a motor in an OL1 condition severely risks damage to motor windings and insulation, leading to premature motor failure and costly downtime.

OL2

Drive Overload 2 (Ambient Temperature)

An OL2 fault indicates that the drive's internal overload protection level has been automatically reduced because the ambient temperature around the drive exceeds its specified rating, as configured in L8-12. This protects the drive's output power components from overheating under high load conditions. Continuous operation in an overly warm environment can lead to component degradation and drive failure.

OL3

Overtorque Detection 1

The Drive output current exceeded the threshold set in L6-02 for longer than the time set in L6-03, indicating a motor overload condition. This fault protects the motor and mechanical system from damage due to excessive load.

OL4

Overtorque 2 Fault

This fault indicates that the motor load has exceeded the configured Overtorque 2 detection level (L6-05) for the set duration (L6-06). Similar to OL3 but using a secondary profile, it triggers based on L6-04 settings, causing the drive to shut down. This points to a mechanical obstruction, jamming, or excessive resistance in the driven equipment. If persistent, this can lead to motor and drive damage or mechanical failure of the connected machinery.

OPE01

kVA Selection Error

An Operator Programming Error occurs when the Drive's kVA setting is incorrect, usually after a control board replacement. The Drive will not operate until this parameter is corrected.

OPE02

Constant Data Out of Range

An Operator Programming Error indicating a parameter has been set above its allowable range. The Drive will not operate until the parameter is set correctly.

OPE03

Multi-function Input Selection Fault

An Operator Programming Error due to duplicate multi-function input selections, conflicting up/down commands, or simultaneous speed search from maximum frequency and set frequency. The Drive will not operate until parameters are corrected.

OPE05

Run Command Sequence Selection Fault

An Operator Programming Error where a run command is selected via serial communication (2CN) but no option board is installed, or it's installed incorrectly. The run command selection parameter B1-02 is set to 3 but the option board is absent. The Drive cannot operate without the correct board and settings.

OPE10

V/f Data Setting Fault

An Operator Programming Error indicating incorrect V/f parameter settings. This can happen if a minimum frequency/voltage value is set higher than the maximum frequency/voltage. The Drive will not operate until corrected.

OPE11

Carrier Frequency Data Setting Fault

An Operator Programming Error related to incorrect carrier frequency parameter settings, such as C6-05 > 6 and C6-04 > C6-03, or an upper/lower limit error for C6-03 (e.g., set above 5.0kHz). The Drive will not operate until corrected.

OPR

Digital Operator Connection Fault

The Drive stopped because the digital operator was removed while the Drive was commanded to run through it. This indicates either the operator is not attached, its connector is broken, or parameter o2-06 is set incorrectly, preventing proper control.

OS

Overspeed

An Overspeed (OS) fault occurs when the motor speed feedback, typically from the PG, exceeds the configured overspeed detection level (F1-08) for a duration longer than the delay time (F1-09). This indicates the motor is running faster than its allowed maximum, potentially due to incorrect control parameters, regenerative load conditions, or an encoder issue. Unresolved overspeed can lead to mechanical damage to the motor or driven equipment, and create safety hazards.

OV

DC Bus Overvoltage

The DC bus voltage exceeded its trip point (≥400Vdc for 208-240Vac Drives; ≥800Vdc for 480Vac Drives). This is often caused by high input voltage, overly short deceleration times leading to regenerative energy, or the presence of power factor correction capacitors on the input. Overvoltage can severely damage drive components.

PF

Input Phase Loss

The Drive input power supply has an open phase or a large imbalance of input voltage. This can be caused by a missing phase, loose terminal screws, momentary power loss, or significant input voltage fluctuations. Operating with phase loss can lead to drive component stress and damage.

PGO

PG Open Circuit

This fault occurs when an open circuit condition is detected in the Pulse Generator (PG) feedback. This means the drive is not receiving proper speed or position feedback from the motor's encoder. This can lead to uncontrolled motor speed, position errors, or loss of precise control if left unaddressed.

PIFB-AL

PI Feedback Loss Alarm

This alarm occurs when the PI function's feedback signal is determined to be lost, as configured by parameter b5-12 set to '1: Alarm'. The drive acknowledges the loss of feedback but continues to operate without stopping, and it does not energize the fault output (MA-MB), indicating a degraded control state rather than a critical shutdown.

PIFB-FL

PI Feedback Loss Fault

This fault occurs when the PI function's feedback signal is determined to be lost, as configured by parameter b5-12 set to '2: Fault'. Upon detection, the drive will coast to a stop and energize the fault output (MA-MB), indicating a critical loss of process control feedback that requires immediate attention.

PUF

DC Bus Fuse Open

The Drive detects that the DC bus fuse has opened. This is typically caused by shorted output transistor(s) or output terminals, indicating a severe internal fault in the power circuit. The fuse opens to protect upstream components but requires addressing the underlying short.

RH

Dynamic Braking Resistor Overload

The protection for the dynamic braking resistor, based on setting of L8-01, has been activated. This fault is typically caused by an overhauling load, an extended dynamic braking duty cycle that exceeds the resistor's capacity, or a defective dynamic braking resistor, leading to overheating.

RR

Dynamic Braking Transistor Fault

This fault indicates a failure of the dynamic braking transistor. Common causes include a shorted dynamic braking transistor, consistently high DC bus voltage, or a defective dynamic braking resistor. This condition can lead to uncontrolled energy dissipation or damage to the drive's power stage.

SVE

Zero Servo Fault

The motor position moved more than 10,000 revolutions during zero servo operation, indicating a loss of position control. This can be caused by an excessively small torque limit, an overly large load torque, or a fault within the control circuit, possibly due to electrical noise interfering with position feedback.

UL3

Undertorque Detection 1

The Drive output current dropped below the threshold set in L6-02 for longer than the time set in L6-03, indicating a motor underload condition. This often signifies a mechanical failure such as a broken belt or coupling, or a sudden loss of load on the motor.

UL4

Undertorque Detection 2

Similar to UL3, this fault indicates the drive's output current was below the L6-05 threshold for longer than L6-06, with L6-04 set for undertorque detection. It signifies a motor running under an unexpectedly light load condition, potentially indicating a process issue or mechanical failure that needs investigation.

UV

Undervoltage Alarm

An Undervoltage (UV) alarm is displayed on the digital operator during a momentary power loss event, specifically after power loss but before a fault trip occurs. This indicates that the drive is actively attempting to ride through the power loss, maintaining operation as long as control power is sustained. It's a warning, not a fault that stops the drive immediately.

UV1

DC Bus Undervoltage

The DC bus voltage fell below its trip point (≤190Vdc for 208-240Vac Drives; ≤380Vdc for 480Vac Drives). This is often due to low input voltage at the R/L1, S/L2, and T/L3 terminals, an acceleration time set too short, or excessive input voltage fluctuations, risking drive instability or shutdown.

UV2

Control Power Supply Undervoltage

An undervoltage condition was detected in the drive's internal control circuit while it was operating. This fault typically points to either an excessive load being drawn by external control wiring connected to the drive's power supplies, or an internal electrical fault, such as a short circuit, on the power or gate drive PCB.

UV3

Soft Charge Circuit Fault

The pre-charge contactor, responsible for managing the initial charging of the DC bus capacitors, opened unexpectedly while the drive was running. This often indicates a mechanical issue with the contactor itself, such as dirty or worn contacts, preventing proper mechanical operation or causing premature opening.