SI-F/G Communication Error Detected
Yaskawa · F7 Drive
What does E-15 mean?
A communication error has occurred when the SI-F/G Option Card is designated as the source for run commands or frequency reference (b1-01=3 and/or b1-02=3), and communication with it is lost. This implies a failure in the communication link or configuration with the SI-F/G card. Without proper communication, the Drive cannot receive critical commands or references, leading to a stop.
Common Causes
- Loss of physical connection to the SI-F/G option card or damage to the communication cable.
- Incorrect communication protocol or address settings (e.g., P5-01, P5-02 for network address) on the SI-F/G card or the master device.
- Excessive network traffic or electromagnetic interference causing data corruption or timeouts on the communication bus.
- The master device (e.g., PLC) stops sending commands or reference signals to the SI-F/G card.
- Hardware malfunction of the SI-F/G option card, preventing it from processing communication.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Inspect the communication cable (e.g., Ethernet, DeviceNet, Profibus) connected to the SI-F/G option card for secure connections and physical damage.
- 2
Verify the communication parameters (e.g., P5-01, P5-02, P5-03) on the Drive's SI-F/G card match the settings on the master controller.
- 3
Confirm the master controller (e.g., PLC) is active and sending run commands/frequency references as expected to the SI-F/G card.
- 4
Temporarily cycle power to the Drive and the master controller to reset communication modules.
- 5
Check for network activity lights (e.g., Link/Act LEDs) on the SI-F/G card itself to confirm physical layer communication.