OH

Heatsink Overheat

Yaskawa · F7 Drive

What does OH mean?

The temperature of the Drive's heatsink has exceeded the programmed setpoint (L8-02, L8-03=0 to 2), indicating inadequate cooling or excessive ambient temperature. This can be caused by a nearby heat source, dirt buildup on fans/heatsink, or high room temperature. Persistent overheating will lead to nuisance trips, reduced performance, and can significantly shorten the Drive's lifespan.

Common Causes

  • Blocked cooling fan or clogged heatsink fins with dust, lint, or debris, restricting airflow.
  • Excessive ambient temperature in the control cabinet exceeding the Drive's specified operating range.
  • Drive cooling fan failure, preventing proper heat dissipation from the heatsink.
  • Drive enclosure ventilation issues (e.g., blocked cabinet vents, improperly sized cooling system).
  • Continuous operation at high load (near or above rated current) for extended periods.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Power down the Drive and visually inspect the heatsink fins for accumulation of dust, lint, or debris. Clean thoroughly using compressed air or a soft brush.

  2. 2

    2. Check the Drive's cooling fan for proper operation (audible and visible rotation). If faulty, replace the fan assembly.

  3. 3

    3. Verify the ambient temperature inside the control cabinet does not exceed the Drive's specified maximum operating temperature (e.g., 50°C).

  4. 4

    4. Inspect the control cabinet's ventilation system (filters, fans, air conditioners) to ensure adequate airflow and heat exchange.

  5. 5

    5. Confirm parameters L8-02 (Heatsink Overheat Level) and L8-03 (Heatsink Overheat Filter Time) are appropriately set, ensuring L8-03 is not set to a value that would prevent proper detection.

Browse all codes in this manual (63)
Verified technical data. Last updated: March 2026

Related Faults