Otis DSD 412 Elevator System

57 Fehlercodes dokumentiert

117/118

SERIAL COMMUNICATION FAULT

Code 117 indicates serial communication did not start within 10 seconds after drive reset or power-up. Code 118 indicates a valid serial communication message was not received for more than 150 ms.

400

MOTOR OVERLOAD FAULT

This fault indicates that the DSD 412 drive has supplied excessive motor current for a significant duration. This condition does not automatically shut down the drive but is signaled via the ALARM relay output K2.

401

EXCESSIVE FIELD CURRENT

This fault signifies that the measured motor field current has exceeded 125% of the rated current, as defined by parameter #50. This condition can lead to motor field damage.

402

LOOP CONTACTOR FAULT

The DSD 412 drive detects that the Loop Contactor auxiliary contact failed to pick up or drop out within the expected timeframe. This behavior is governed by the setting of parameter #102.

403

FIVE-MINUTE FULL FIELD

This fault indicates that the Drive and Field Enable control circuit at terminal TB1-9 remained active for five minutes without the drive commencing operation. This condition can lead to burnout of the motor field winding.

404

OPEN ARMATURE CIRCUIT

This fault occurs when a large current error is detected in the armature circuit and persists for half a second. This indicates a break in the armature current path.

405

SAFETY CIRCUIT FAULT

The DSD 412 drive detects that the Safety Circuit, connected between terminals TB3-1 and TB3-6 on the power supply, unexpectedly opened while the drive was in run mode. The safety chain must be closed for at least 100ms before enabling the drive. This fault is disabled if the speed is below the low speed threshold defined by parameter #64.

406

LOW LINE ALARM

This alarm indicates that the input AC line voltage has sagged more than 10% below the nominal line voltage, as configured by parameter #9. This is a warning and does not automatically shut down the DSD 412 drive, but it suggests that preventative action may be required to avoid future F904 Low Line shutdown faults.

407

DCU CEMF FAULT

This fault indicates that the Counter-Electromotive Force (CEMF) of the motor has exceeded 109% of the measured AC input voltage supplied to the DSD 412 drive. This is a warning and does not cause an automatic drive shutdown.

408

PCU CEMF FAULT

The Counter Electromotive Force (CEMF) of the motor exceeded 118% of the rated VAC input voltage to the drive. This fault causes a drive shutdown to prevent fuse blowing.

409

UNEXPECTED PCU RESET

The PCU processor was unexpectedly reset.

410

SPEED ERROR TRIP FAULT

This fault causes an automatic drive shutdown when speed errors exceed the threshold defined by Function #100 for a duration longer than specified by Function #99 (Speed Error Trip Time).

411

MAXIMUM AUTO RESETS FAULT

This fault is triggered when an accumulation of five counted faults occurs. Once this fault is active, manual intervention is required to reset the drive and continue operation.

413

FIELD CURRENT TRACKING FAULT

The actual field current failed to track the field current command by more than F192 (Default = 0.05) for 5 seconds. This condition is a warning and is not a shutdown fault.

414

SOFTWARE COMPATABILITY FAULT

The PCU (U13, U14) Version or Revision software is incompatible with the DCU (U39, U40) installed in the drive.

900

PCU LOOP FAULT

The contactor did not close or opened unexpectedly, or the motor voltage exceeded 30% of rated motor voltage #7 during Self-Tune #997. This fault sets the Severe Fault flag and forces the DSD 412 current reference to zero, leading to a drive shutdown.

901

PCU IST FAULT

Current flow in excess of 300% of the rated armature current has been detected.

902

POWER SUPPLY FAULT

The Low Voltage Power Supply (A4) output has dropped below 60% of the rated voltage. This fault requires a CPU Reset and will shut down the drive.

903

LINE SYNC FAILURE

The Phase Locked Loop has lost synchronization with the 3 Phase AC input power supply. This sets the Severe Fault flag and forces the current reference to zero, shutting down the drive. It is generally caused by AC input power problems and is often self-correcting, frequently occurring with an F904 fault.

904

LOW LINE VOLTAGE FAULT

The AC input power has dropped below 80% of the Nominal AC Line Voltage #9 for 3 consecutive cycles or lower than 50% for one cycle. This sets the Severe Fault flag and forces the DSD 412 current reference to zero, shutting down the drive.

905

FIELD LOSS FAULT

The field current feedback has dropped below 80% of the expected current during specific operating conditions: Field Weakening Mode (Top speed, #49), Full Field Mode (Accel or Decel, #50), or Standing Field Mode (not running, #53). This fault will shut down the drive.

906

DCU FAILURE FAULT

The update of the Dual Port RAM from the Drive Control Unit (DCU) is unreliable. This fault will shut down the drive and requires a DSD 412 power down before attempting corrective actions.

907

THERMISTOR FAULT

The thermistor is found to be open or shorted. This fault can also occur if the machine room ambient temperature is below 0°C (as the resistance detected is too high) or if an open thermostat is present on larger drives. This fault will not shut down the drive.

908

OVER TEMPERATURE FAULT

The calculated SCR junction temperature is above 125 degrees Centigrade. This is derived from the thermistor heat sink measurement combined with the heating effects of measured armature output current on the SCRs. This fault will not shut down the drive.

909

RIPPLE FAULT

Repeated high peak to average motor armature current is detected. This condition may be caused by defective hardware, poor regulator tuning, or other oscillatory operation conditions.

910

BLOWN FUSE FAULT

One or more of the three AC line fuses is open. This condition is checked on power-up and can be confirmed upon request through the PCU F#998 PCU Diagnostics function, via measurements on the Armature Interface PCB, A2.

911

SHORTED SCRS/DOUBLER FAULT

One of the SCR/Doubler packs has a short circuit between the SCRs. This condition is checked only upon request through the PCU #998 Diagnostics CDU function. The optional handheld PCDU can identify which specific SCR pair is faulty. This fault requires a DSD Power Down.

912

OPEN SCR FAULT

One of the SCRs does not conduct current as expected. This condition is checked only upon request through the PCU #998 Diagnostics CDU function. The optional handheld PCDU can identify which specific SCR pair is faulty. This fault requires a DSD Power Down.

915

PARAMETER SETUP FAULT

One of the following parameters is not within the acceptable range of the chassis hardware: Rated Volts #7 or #9, or Rated Current #3 or #50. This fault requires a DSD power down.

916

FORCING FAULT

The prohibit rotation bit was removed while the loop was picked-up. This fault can only occur when using the handheld PCDU, indicating an incorrect operational sequence.

917

REVERSE ARMATURE POLARITY

The polarity of the Armature Voltage Feedback wires is reversed or the wires are missing. This fault shows up during the F998 PCU Diagnostics Test and can cause F909 faults or very poor drive/ride performance if not corrected. This fault requires a DSD power down.

919

LINE VOLTAGE SETTING FAULT

This fault is declared if a number entered for the Rated Line Voltage, #9, is outside the acceptable range of 150 to 525VAC. If 0 is entered, the rated line voltage defaults to 230 or 460 VAC depending on the line voltage sensed. This fault requires a DSD power down.

920

LOAD VOLTAGE SETTING FAULT

This fault is declared if the Rated Armature Voltage, #7, value is outside the acceptable range of 150 to 700 VDC. This fault requires a DSD power down.

921

BRIDGE RATING FAULT

The drive's computer cannot identify the drive size. The bridge type is determined by a sense resistor on the Cube ID PCB (plugged into the A2 Armature Interface PCB), which identifies the ampere rating and current feedback scaling of the physical hardware. This fault occurs if the sense resistor value is not recognized. This fault requires a DSD power down.

923

LOAD CURRENT SETTING FAULT

This fault is declared if a number entered for Rated Armature Current, #3, is outside the acceptable range of 0.125 to 2.0 times the bridge current rating. The bridge current rating is determined by the bridge sense resistor on the Cube ID PCB, located on the Armature Interface PCB. This fault requires a DSD power down.

924

FIELD CURRENT SETTING FAULT

This fault is declared if a number entered for Rated Field Current #50 is outside the acceptable range of the Field Interface board, A3, current rating. This rating is determined by the field sense resistor selected by SW1 on the Field Interface PCB. This fault requires a DSD power down.

925

FIELD SENSE FAULT

The field bridge rating is determined by reading a sense resistor on the Field Interface board selected by SW1. If the resistance value is not recognized, a Field Sense Fault is declared, indicating a hardware fault. This fault requires a DSD power down.

926

PCU WATCHDOG TIMEOUT FAULT

A problem exists with either hardware or software on the Drive Control PCB, which can lead to a PCU watchdog timeout.

930

Motor field current does not increase to near rated amperes within 6 seconds.

This fault indicates that the motor field current failed to reach near its rated amperes within 6 seconds during testing. This condition may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998) routines.

931

Excessive open circuit voltage to motor armature circuit.

This fault occurs when the measured armature voltage is greater than 10% of the rated volts (parameter #7) during an open circuit test. It may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).

932

Armature CEMF volts >20% of rated during test.

This fault indicates that the Armature CEMF voltage exceeds 20% of its rated value during a test. This condition may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).

933

Motor armature current does not increase to near test amps within 6 seconds.

This fault indicates that the motor armature current failed to reach near the specified test amperes within 6 seconds. This may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).

934

Calculated armature inductance is less than 0.00017 Henry.

The DSD 412 drive will not perform Self-Tune if the calculated load inductance is less than 170 micro-henries. This fault may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).

935

Calibration of bus voltage and armature voltage feedback circuits does not match.

This fault indicates a mismatch in calibration between the bus voltage and armature voltage feedback circuits. It may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).

936

E-Stop contact was opened during test.

This fault indicates that the E-Stop circuit was opened during a Self-Tune (Function #997) or Self-Diagnostic (Function #998) test, rendering the test data invalid.

937

Low read-back volts from motor armature circuit.

This fault indicates that a low voltage read-back is detected from the motor armature circuit. This can occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).

938

Low read-back volts from DC bus circuit.

This fault indicates that a low voltage read-back is detected from the DC bus circuit. This can occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998). For drives larger than 300 amps DC, this involves discrete wires.

939

Faulty Field Control Hardware.

This fault indicates a problem with the field control hardware. It may only occur during the power-up sequence.

940

Field Current Feedback A/D Saturated

This fault occurs when the Field Analog-to-Digital (A/D) converter reading remains saturated for more than 15 seconds, indicating an issue with the field current feedback circuit.

941

MOTOR THERMOSTAT FAULT

This fault indicates that the DSD 412 drive has detected an open motor thermostat circuit, specifically between terminals A4TB3(2) and A4TB3(8). This condition does not automatically shut down the drive but is annunciated via the ALARM relay output K2.

97

OVERSPEED FAULT

The motor speed has exceeded the trip level set in parameter #12, as measured by the encoder. Parameter #12 defines a percentage of the motor speed value set in parameter #11.

98

TACH LOSS FAULT

The drive does not detect encoder velocity in proportion to the armature voltage indication of speed. Refer to Function explanations for parameters #14 and #15.

99

REVERSED TACH FAULT

The digital encoder signals and motor voltage signals do not agree in their detected direction of rotation.

F910

BLOWN FUSE

This fault is detected by the PCU Diagnostics function (Function #998) and indicates that one or more AC line fuses are open within the DSD 412 drive power conversion unit.

F911

SHORTED SCR

This fault is detected by the PCU Diagnostics function (Function #998) and indicates that one or more SCRs (Silicon Controlled Rectifiers) or doubler packs within the DSD 412 drive are shorted.

F912

OPEN SCR

This fault is detected by the PCU Diagnostics function (Function #998) and indicates that one or more SCRs (Silicon Controlled Rectifiers) or doubler packs within the DSD 412 drive are open, meaning they are not conducting current as expected.

F917

REVERSE ARM. V. FEEDBACK

This fault is detected by the PCU Diagnostics function (Function #998) and indicates that the Armature Feedback wires are either reversed or not connected at all.