408
PCU CEMF FAULT
Otis · DSD 412 Elevator System
Was bedeutet 408 ?
The Counter Electromotive Force (CEMF) of the motor exceeded 118% of the rated VAC input voltage to the drive. This fault causes a drive shutdown to prevent fuse blowing.
Häufige Ursachen
- Low 3 Phase Input AC Line Voltage.
- Incorrect motor field current setting or field regulator mis-operation causing excessive CEMF.
- Excessive drive speed overshoot.
- Poor motor field control dynamic tuning.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Measure and correct the 3 Phase Input AC Line Voltage.
- 2
Check motor field current setting and field regulator operation.
- 3
Adjust velocity regulator to correct excessive drive speed overshoot.
- 4
Review and verify settings for parameters #49, #50, #51, #52, #54, and #55 to correct motor field control dynamic tuning.