Übersetzen...
408

PCU CEMF FAULT

Otis · DSD 412 Elevator System

Was bedeutet 408 ?

The Counter Electromotive Force (CEMF) of the motor exceeded 118% of the rated VAC input voltage to the drive. This fault causes a drive shutdown to prevent fuse blowing.

Häufige Ursachen

  • Low 3 Phase Input AC Line Voltage.
  • Incorrect motor field current setting or field regulator mis-operation causing excessive CEMF.
  • Excessive drive speed overshoot.
  • Poor motor field control dynamic tuning.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure and correct the 3 Phase Input AC Line Voltage.

  2. 2

    Check motor field current setting and field regulator operation.

  3. 3

    Adjust velocity regulator to correct excessive drive speed overshoot.

  4. 4

    Review and verify settings for parameters #49, #50, #51, #52, #54, and #55 to correct motor field control dynamic tuning.

Alle Codes in diesem Handbuch durchsuchen (57)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes