26

Startup Prevented

Vacon · 100 FLOW Application Guide

What does 26 mean?

The drive cannot perform a startup because a new software (firmware or application), parameter setting, or other file affecting operation was loaded while a Run request was ON. The drive prevents startup to ensure configuration integrity and prevent improper operation.

Common Causes

  • A firmware update or parameter upload was performed while a run command (e.g., DI1 active, P0-10 = 1) was still present.
  • Application program was loaded or changed with the drive in a 'Ready' state, not 'Stopped' or 'Faulted'.
  • Changes to critical safety parameters or hardware configuration (e.g., option board change) were saved without cycling power.
  • Parameter setting download from an external tool (e.g., DriveWorks) occurred while the drive was expecting a run command.
  • Persistent run command signal (e.g., stuck digital input, communication bit) remained active during a configuration change.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Cycle the main input power to the drive (power off, wait for DC link discharge, power on).

  2. 2

    Ensure that any run command signals (e.g., digital input terminal 1 (DI1), communication command) are deactivated before attempting further configuration changes.

  3. 3

    Verify that no external control system is sending a persistent run command. Temporarily disconnect control wiring from terminals like DI1 to rule this out.

  4. 4

    Re-check the drive's run/stop source parameter (e.g., P0-10) to ensure it is correctly configured for the desired control method (e.g., HMI, DI, fieldbus).

  5. 5

    If a parameter file was recently uploaded, ensure the correct file version for the current application is active after cycling power.

Browse all codes in this manual (73)
Verified technical data. Last updated: March 2026

Related Faults

Source: Vacon 100 FLOW Application Guide