Fronius Primo GEN24

60 feilkoder dokumentert

102

AC voltage too high

The AC grid voltage at the inverter's connection point is too high, exceeding the permitted limits for the Fronius Primo GEN24 208-240 inverter. This condition can lead to the inverter disconnecting from the grid to protect itself and the system.

103

AC voltage too low

The AC grid voltage at the inverter's connection point has fallen below the permitted limits for the Fronius Primo GEN24 208-240 inverter. This can cause the inverter to disconnect from the grid, preventing proper power feed-in.

104

AC frequency too high

The frequency of the AC grid at the inverter's connection point has exceeded the maximum allowable limit for the Fronius Primo GEN24 208-240 inverter. The inverter will disconnect from the grid to ensure stability and protection.

105

AC frequency too low

The frequency of the AC grid at the inverter's connection point has dropped below the minimum allowable limit for the Fronius Primo GEN24 208-240 inverter. This condition will cause the inverter to disconnect to prevent damage or improper operation.

106

Overcurrent on AC side

The Fronius Primo GEN24 208-240 inverter has detected an overcurrent condition on its AC output, meaning the current flowing into the grid is higher than permitted. This fault indicates a potential short circuit or overload condition in the AC connection or grid.

107

Grid failure (e.g. blackout)

The Fronius Primo GEN24 208-240 inverter has detected a general failure in the AC grid, such as a blackout or complete loss of grid voltage, preventing it from feeding power. The inverter will automatically disconnect from the grid for safety and will attempt to reconnect once grid conditions normalize.

108

Grid failure (general)

The Fronius Primo GEN24 208-240 inverter has detected an unspecified general failure in the AC grid, which could encompass various grid instability issues beyond simple voltage or frequency deviations. The inverter will disconnect from the grid as a protective measure.

109

Incorrect grid type / no grid connected

The Fronius Primo GEN24 208-240 inverter has detected that the connected grid type is not supported or that no AC grid is connected. This prevents the inverter from synchronizing and feeding power.

301

Insulation fault on PV generator (PV1)

The Fronius Primo GEN24 208-240 inverter has detected an insulation fault (ground fault) on the PV generator (PV1 string). This means there is an unintended electrical path between the PV array's DC conductors and ground, posing a safety risk and preventing power production.

302

Insulation fault on PV generator (PV2)

The Fronius Primo GEN24 208-240 inverter has detected an insulation fault (ground fault) on the PV generator (PV2 string). This indicates an unintended electrical path between the PV array's DC conductors and ground, which is a safety hazard and stops power generation.

303

Insulation fault on PV generator

The Fronius Primo GEN24 208-240 inverter has detected a general insulation fault (ground fault) on the entire PV generator. This implies an unintended electrical path between the PV array's DC conductors and ground, which can be a safety risk and prevents inverter operation.

401

No communication with Fronius Smart Meter

The Fronius Primo GEN24 208-240 inverter is unable to establish communication with the connected Fronius Smart Meter. This prevents accurate energy monitoring and management functions that rely on meter data.

402

No communication with battery

The Fronius Primo GEN24 208-240 inverter cannot establish communication with the connected battery system. This prevents the inverter from managing battery charging, discharging, and monitoring, rendering the battery inoperable.

403

Inverter with Smart Meter: no communication

The Fronius Primo GEN24 208-240 inverter, configured for operation with a Smart Meter, has lost communication with the device. This fault specifically refers to configurations where a Smart Meter is essential for the operating mode, thus halting normal inverter function.

404

Inverter with battery: no communication

The Fronius Primo GEN24 208-240 inverter, configured to operate with a battery, has lost communication with the battery system. This prevents any battery charging or discharging, effectively disabling the energy storage function.

502

Overcurrent on DC side (PV1)

The Fronius Primo GEN24 208-240 inverter has detected an excessive current flowing from the PV1 string on the DC side. This indicates a potential short circuit within the PV1 array or an incorrect string configuration.

503

Overcurrent on DC side (PV2)

The Fronius Primo GEN24 208-240 inverter has detected an excessive current flowing from the PV2 string on the DC side. This suggests a potential short circuit within the PV2 array or an improper string configuration.

504

Overcurrent on DC side (Battery)

The Fronius Primo GEN24 208-240 inverter has detected an excessive current flowing to or from the connected battery system on the DC side. This indicates a potential short circuit in the battery DC wiring or an issue with the battery itself.

505

Overvoltage on DC side (PV1)

The Fronius Primo GEN24 208-240 inverter has detected an excessively high voltage from the PV1 string on the DC side, exceeding its maximum input voltage rating. This can lead to inverter damage.

506

Overvoltage on DC side (PV2)

The Fronius Primo GEN24 208-240 inverter has detected an excessively high voltage from the PV2 string on the DC side, exceeding its maximum input voltage rating. This poses a risk of damage to the inverter's DC-DC stage.

507

Overvoltage on DC side (Battery)

The Fronius Primo GEN24 208-240 inverter has detected an excessively high voltage from the connected battery system on the DC side, exceeding its maximum input/output voltage rating. This could indicate a battery management system (BMS) fault or an incompatible battery.

509

DC voltage too low (PV1)

The Fronius Primo GEN24 208-240 inverter has detected that the DC voltage from the PV1 string is too low for operation. This means there is insufficient voltage to start or maintain power conversion, often due to low irradiance or issues with the PV array.

510

DC voltage too low (PV2)

The Fronius Primo GEN24 208-240 inverter has detected that the DC voltage from the PV2 string is too low for operation. This indicates insufficient voltage for power conversion, often caused by low sunlight or problems within the PV array.

512

DC voltage too low (Battery)

The Fronius Primo GEN24 208-240 inverter has detected that the DC voltage of the connected battery system is too low. This indicates the battery is deeply discharged or has an internal fault, preventing it from supplying power or being charged.

601

Fan fault

The Fronius Primo GEN24 208-240 inverter has detected a fault with its internal cooling fan. This can lead to insufficient cooling and subsequent overheating if not addressed, potentially reducing performance or causing shutdown.

603

Over temperature

The Fronius Primo GEN24 208-240 inverter has detected an internal temperature exceeding its safe operating limits. This protective measure prevents damage to internal components and will cause the inverter to reduce power or shut down.

604

No communication with internal components

The Fronius Primo GEN24 208-240 inverter has lost communication with one or more of its critical internal components. This indicates an internal hardware issue, preventing the inverter from functioning correctly.

701

Internal fault

The Fronius Primo GEN24 208-240 inverter has detected a general internal fault that prevents it from operating safely or correctly. This is a broad error indicating an unspecified hardware or software malfunction within the inverter itself.

702

Internal fault (e.g. communication module)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault specifically related to its communication module or other critical internal components. This prevents data exchange and potentially affects overall inverter operation.

703

Internal fault (e.g. sensor)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault, specifically indicating an issue with one of its internal sensors. This can lead to incorrect measurements, improper control, or a complete shutdown for protection.

704

Internal fault (e.g. main board)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault, likely related to its main control board. This is a critical error indicating a severe hardware malfunction that prevents any normal operation of the inverter.

705

Internal fault (e.g. software)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault, specifically related to its software. This can lead to unexpected behavior, incorrect operation, or a complete system halt.

706

Internal fault (e.g. hardware protection)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault related to its hardware protection circuits. This is a critical error, indicating that a safety mechanism has been triggered due to a potentially dangerous condition within the inverter, preventing further operation.

707

Internal fault (e.g. temperature sensor)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault specifically concerning a temperature sensor. This can lead to inaccurate temperature monitoring, improper fan control, or a safety shutdown to prevent overheating or damage.

708

Internal fault (e.g. DC measurement)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault related to its DC measurement circuitry. This means that the inverter cannot accurately measure the DC voltage or current from the PV strings or battery, leading to improper operation or shutdown.

709

Internal fault (e.g. AC measurement)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault related to its AC measurement circuitry. This prevents the inverter from accurately measuring AC voltage, current, or frequency, leading to an inability to synchronize with the grid or feed power.

710

Internal fault (e.g. internal power supply)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault within its internal power supply unit. This means that critical internal circuits are not receiving stable or correct power, leading to general malfunction or complete shutdown.

711

Internal fault (e.g. communication to display)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault related to the communication with its display unit. While the inverter itself might be operating, the display may not show correct information or any information at all.

712

Internal fault (e.g. DC disconnector)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault associated with its integrated DC disconnector. This indicates a potential malfunction of the disconnector or its internal sensing, preventing safe and reliable operation.

713

Internal fault (e.g. surge protection device)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault related to its surge protection device (SPD). This indicates that the SPD may have failed, potentially due to a voltage surge, compromising the inverter's protection against transient overvoltages.

714

Internal fault (e.g. system monitoring)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault within its system monitoring module. This can prevent the inverter from accurately tracking its performance, logging data, or providing status updates.

715

Internal fault (e.g. residual current monitoring unit)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault within its residual current monitoring unit (RCMU). This unit is crucial for detecting ground faults and ensuring safety. A fault here means the inverter cannot safely operate and will shut down.

716

Internal fault (e.g. arc fault detection)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault within its arc fault detection (AFCI) or Arc Guard circuit. This system is essential for detecting dangerous electrical arcs in the PV array and shutting down for safety. A fault means this protection is compromised.

717

Internal fault (e.g. PV Power Point Tracker)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault within its Maximum Power Point Tracker (MPPT) for the PV strings. This means the inverter cannot efficiently extract maximum power from the PV array, leading to reduced energy yield or complete shutdown.

718

Internal fault (e.g. battery charging/discharging)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault related to its battery charging or discharging circuitry. This prevents the inverter from effectively managing the flow of power to and from the connected battery system.

719

Internal fault (e.g. startup)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault during its startup sequence. This means the inverter is unable to complete its initialization process and begin normal operation.

720

Internal fault (e.g. relay)

The Fronius Primo GEN24 208-240 inverter has detected an internal fault related to one of its output relays. These relays are crucial for safely connecting and disconnecting the inverter from the grid. A fault here prevents proper grid connection.

721

Internal fault (e.g. general hardware)

The Fronius Primo GEN24 208-240 inverter has detected a general internal hardware fault that is not covered by more specific error codes. This indicates a broad malfunction within the inverter's electronic components, preventing normal operation.

801

AFCI (Arc Fault Circuit Interrupter) event

The Fronius Primo GEN24 208-240 inverter's Arc Fault Circuit Interrupter (AFCI) has detected a dangerous electrical arc in the PV array. This is a critical safety feature that shuts down the inverter to prevent fire hazards.

802

AFCI (Arc Fault Circuit Interrupter) self-test error

The Fronius Primo GEN24 208-240 inverter's Arc Fault Circuit Interrupter (AFCI) has failed its internal self-test. This means the AFCI function, a critical safety feature, is not working correctly, and the inverter cannot operate safely.

901

Backup power operation not possible

The Fronius Primo GEN24 208-240 inverter is unable to switch to or maintain backup power operation (PV Point or Essential Backup). This means the system cannot provide emergency power to critical loads during a grid outage.

902

DC voltage too low for backup power

The DC voltage from the battery is too low to initiate or sustain backup power operation with the Fronius Primo GEN24 208-240 inverter. This indicates the battery is either critically discharged or faulty.

903

Backup power overcurrent

The Fronius Primo GEN24 208-240 inverter has detected an overcurrent condition on the backup power circuit. This means that the loads connected to the backup power output are drawing more current than the inverter or battery can safely supply, leading to a shutdown.

904

Battery communication lost during backup

The Fronius Primo GEN24 208-240 inverter has lost communication with the connected battery system while operating in backup power mode. This critical failure prevents the inverter from managing battery power, leading to a backup power shutdown.

905

Grid failure (PV Point)

The Fronius Primo GEN24 208-240 inverter has detected a grid failure specific to the PV Point backup power function. This implies that while the main grid might be active, the specific conditions required for the PV Point to operate are not met, or there's a problem with the transfer to PV Point.

906

Too many inverters in Essential Backup system

The Fronius Primo GEN24 208-240 inverter has detected that there are too many inverters configured or connected within the Essential Backup system. This can lead to instability or an inability to properly manage power in backup mode. The Essential Backup system typically supports a limited number of inverters.

1030

WSD Open

This status code, indicated by a flashing red operating LED on the Fronius Primo GEN24 inverter, signifies that a device within the Wired Shutdown (WSD) chain has interrupted the signal line. This can occur if a surge protection device (SPD) has tripped, the factory-installed bypass has been removed, or a trigger device is not properly installed.

1083

Insulation Fault / Low Insulation Resistance

This status code is displayed on the user interface of the Fronius Primo GEN24 inverter if the measured insulation value drops below the configured "Threshold for the insulation warning". This indicates a potential insulation fault within the PV array or DC wiring. The insulation warning can be activated or deactivated, and the measurement mode (Exact/Fast) and threshold (100000 - 10000000 Ω) are configurable parameters.

1177

Maximum Backup Power Restart Attempts Reached

Service message 1177 indicates that the Fronius Primo GEN24 inverter has reached the maximum number of automated restart attempts in backup power mode. This limit is set by the "Backup power restart attempts" parameter (range 1-10). Once this limit is reached, the inverter will not automatically restart backup power mode until the service message is manually acknowledged. This typically occurs after repeated shutdowns due to unstable backup power conditions.

Backup power overload

Backup Power Overload

This status code indicates that the Fronius Primo GEN24 inverter has stopped backup power mode due to excessive loads connected to the PV Point (OP) terminal. The total power demand from connected appliances has exceeded the inverter's maximum continuous output, which is specified as 1560 W at 120V (13 A AC continuous current). Transient overloads up to 35% are tolerated for a maximum duration of 5 seconds.