Oversetter...
105

AC frequency too low

Fronius · Primo GEN24

Hva betyr 105 ?

The frequency of the AC grid at the inverter's connection point has dropped below the minimum allowable limit for the Fronius Primo GEN24 208-240 inverter. This condition will cause the inverter to disconnect to prevent damage or improper operation.

Vanlige årsaker

  • The grid frequency is too low.
  • The grid is unstable.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the AC grid frequency at the inverter's connection point using a frequency meter or a multimeter with frequency measurement capability.

  2. 2

    Determine if the low grid frequency is a persistent issue or a transient event.

  3. 3

    Ensure no local large inductive loads are causing significant frequency deviations.

  4. 4

    Immediately contact the grid operator to report the unstable or low grid frequency, as this points to a potential public grid instability or generation issue.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Fronius 105 (AC frequency too low) — Teknisk referanse | ErrorLib