Oversetter...
106

Overcurrent on AC side

Fronius · Primo GEN24

Hva betyr 106 ?

The Fronius Primo GEN24 208-240 inverter has detected an overcurrent condition on its AC output, meaning the current flowing into the grid is higher than permitted. This fault indicates a potential short circuit or overload condition in the AC connection or grid.

Vanlige årsaker

  • Overcurrent at the AC connection.
  • Short circuit at the AC connection.
  • Malfunction in the inverter's internal current measurement circuitry.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Disconnect the Fronius Primo GEN24 208-240 inverter from the AC grid and visually inspect the AC connection cables and terminals for any signs of damage, short circuits, or loose connections.

  2. 2

    Check the AC cables between the inverter and the grid connection point for insulation breakdown or damage.

  3. 3

    Verify the ratings of external AC overcurrent protection devices (circuit breakers, fuses) are appropriate for the inverter's output.

  4. 4

    Ensure no external loads are causing a short circuit or extreme overload condition directly at the inverter's output if operating in a microgrid setup.

  5. 5

    If the issue persists after external checks, this may indicate an internal fault with the inverter; contact Fronius service.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder