Traduciendo...
25, 94

EEPROM error

SEW Eurodrive · Drives

¿Qué significa 25, 94 ?

An error occurred with the EEPROM (Electrically Erasable Programmable Read-Only Memory) of the MOVIMOT drive. This memory is crucial for storing configuration data, parameters, and operational settings.

Causas comunes

  • Data corruption in the EEPROM
  • Hardware fault of the EEPROM component
  • Issue during parameter saving or loading

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the incoming supply voltage at the MOVIMOT drive input terminals and verify it is within the specified tolerance.

  2. 2

    Check the current drive parameters using appropriate diagnostic software (e.g., MOVITOOLS) and compare them with the machine's configuration backup. If parameters are corrupted or unreadable, attempt to reload a known good parameter set.

  3. 3

    Inspect all communication bus connections (e.g., AS-Interface, PROFINET, PROFIBUS) to the MOVIMOT drive for loose wiring, poor contacts, or electromagnetic interference.

  4. 4

    Verify the firmware version of the MOVIMOT drive and consult SEW Eurodrive documentation for any known issues or recommended updates related to EEPROM errors for that specific firmware.

  5. 5

    Perform a controlled power cycle of the MOVIMOT drive, observing if the EEPROM error clears or persists upon restart.

Ver todos los códigos en este manual (39)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas