Brake chopper error

SEW Eurodrive · Drives

¿Qué significa 04 ?

An error has occurred in the internal brake chopper circuit of the MOVIMOT drive. This circuit is responsible for dissipating regenerative energy generated by the motor during deceleration.

Causas comunes

  • Internal hardware fault of the brake chopper circuit

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the drive's deceleration ramp times and braking parameters are correctly configured for the application load and inertia.

  2. 2

    Inspect any externally connected braking resistor and its associated cabling for proper connection, damage, and correct resistance value (if applicable).

  3. 3

    Measure the DC bus voltage during operation, especially during deceleration, to check for overvoltage conditions.

  4. 4

    Check the drive's diagnostic logs or status screens for additional related fault codes or warnings.

Ver todos los códigos en este manual (39)