0C8A

Error in outgoing MFI interface (OUT1)

SEW Eurodrive · Drives

¿Qué significa 0C8A ?

The outgoing MFI interface (OUT1) was activated even though no station is connected or was configured in the master. This indicates a mismatch between the physical setup and the INTERBUS master configuration.

Causas comunes

  • No station physically connected to the outgoing interface OUT1.
  • Outgoing interface OUT1 not configured in the INTERBUS master.
  • Incorrect setting of DIP switch 6 (NEXT/END) on the MFI.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the setting of DIP switch 6 (NEXT/END) on the MFI. If the MFI is the last station in the bus segment, this switch must be set to END.

  2. 2

    Verify that a station is physically connected to OUT1 if it is enabled.

  3. 3

    Check the INTERBUS master configuration to ensure OUT1 is correctly configured for connected stations.