F031

Incorrect configuration

Schindler · Easy Altivar ATV310 Drive

¿Qué significa F031 ?

This fault indicates that the drive's configuration is inconsistent. It can occur if an HMI block from a drive with a different rating is installed, or if the customer parameters currently loaded are not valid for the drive.

Causas comunes

  • HMI block replaced by an HMI block configured on a drive with a different rating.
  • The current configuration of customer parameters is inconsistent or corrupted.
  • Configuration data integrity issue during power-up or parameter changes.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Return the drive to its factory settings to clear any inconsistent configuration data.

  2. 2

    Retrieve and load a valid backup configuration if one is available and known to be compatible.

  3. 3

    If the fault persists after reverting to factory settings, contact your local Schneider Electric representative for further assistance.