Traduciendo...
F019

Ground short-circuit

Schindler · Easy Altivar ATV310 Drive

¿Qué significa F019 ?

This ATV310 fault indicates a ground fault condition detected in the system, typically at the drive output or within the motor/cabling. This poses a safety risk and can lead to equipment damage if not promptly addressed.

Causas comunes

  • Short-circuit or grounding at the drive output terminals or within the motor windings
  • Ground fault occurring while the drive is in run state
  • Significant current leakage to ground, especially when several motors are connected in parallel to one drive

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Disconnect the motor from the drive and verify the cables connecting the drive to the motor for short circuits (phase-to-phase or phase-to-ground).

  2. 2

    Test the motor insulation resistance using a megohmmeter (megger) to check for ground faults or inter-phase shorts.

  3. 3

    Adjust the switching frequency (parameter 315) to a lower value if transients are suspected to be contributing to the fault.

  4. 4

    Connect chokes in series with the motor if high current leakage to ground is observed or multiple motors are driven by the same VFD.

Ver todos los códigos en este manual (37)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schindler Easy Altivar ATV310 Drive