Traduciendo...
F015

3 Output phases loss

Schindler · Easy Altivar ATV310 Drive

¿Qué significa F015 ?

This ATV310 fault is detected when all three phases on the drive's output to the motor are lost. Common causes include a disconnected motor, a motor with insufficient power relative to the drive, an open output contactor, or transient instability in the motor current during operation.

Causas comunes

  • Motor not connected to the drive output
  • Motor power is too low, below 6% of the rated drive current
  • Output contactor in the motor circuit is open
  • Transient instability in the motor current preventing proper detection
  • Output phase loss detection (parameter 605) is active (set to 01) and conditions for 3-phase loss are met

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check all power connections from the drive to the motor for tightness and proper termination.

  2. 2

    If testing the drive without a motor or with a low-power motor, deactivate motor phase loss detection by setting parameter 605 to 00.

  3. 3

    Check and optimize IR compensation (parameter 310), Rated motor voltage (parameters 304 and 305) for improved motor detection.

  4. 4

    Perform Auto-tuning (parameter 318) to ensure the drive accurately characterizes the connected motor.

Ver todos los códigos en este manual (37)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schindler Easy Altivar ATV310 Drive