Motor phase failure phase U
Lenze · i550 Protec Drive
¿Qué significa 65290 ?
A failure specifically of motor phase U has been detected. This indicates an open circuit in the wiring for phase U between the inverter and the motor, or an issue within the motor's U-phase winding. The error can only be reset after a 2-second blocking time.
Causas comunes
- Broken conductor in motor cable phase U between the inverter output (U) and motor terminal (U1).
- Loose electrical connection at inverter output terminal U or motor terminal U1.
- Internal open circuit in the motor's U-phase winding.
- Failure of the inverter's internal power switching device (IGBT) responsible for phase U output.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
De-energize the drive and lock out power at the main disconnect.
- 2
Disconnect the motor cable from the inverter's U, V, W output terminals.
- 3
Measure the resistance between inverter output terminals U and V, and U and W using a multimeter; expect infinite resistance (open circuit).
- 4
Measure the resistance of the motor's U-phase winding by disconnecting the motor cable from the motor and measuring between motor terminals U1-V1, U1-W1, and V1-W1; verify balanced, low resistance readings.
- 5
Check for continuity of the motor cable conductor for phase U using a multimeter, measuring between the inverter-side U conductor and the motor-side U1 conductor.