User-defined fault (LECOM)
Lenze · i550 Protec Drive
¿Qué significa 25248 ?
This fault indicates that a user-defined 'Activate fault' function has been triggered specifically through the LECOM control word. The activation signal was detected on bit 10 of LECOM control word 0x400B:002 (P592.02). This fault type typically results in the motor being brought to a standstill.
Causas comunes
- The LECOM master (e.g., PLC) has inadvertently or incorrectly set bit 10 of the LECOM control word.
- Programming error within the LECOM master device causing erroneous bit manipulation on the control word.
- Corruption of data on the LECOM communication bus due to electrical noise or poor cable integrity.
- An intermittent fault with the LECOM interface module on either the drive or the master controller, causing bit 10 to be set.
- A user-defined condition within the LECOM master intended to trigger this fault but is activating under unintended circumstances.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Utilize LECOM diagnostic software or a bus analyzer to monitor the state of bit 10 within the LECOM control word.
- 2
Review the PLC program or master controller logic that generates the LECOM control word to identify where bit 10 is being set.
- 3
Verify the physical integrity of the LECOM communication cable (e.g., shielding, termination) to prevent data corruption.
- 4
Cycle power to both the LECOM master and the drive to reset their communication interfaces and clear any transient errors.
- 5
If available, temporarily disable the 'Activate fault' linkage to LECOM control word bit 10 in the drive's parameters to isolate the issue.