231-A003

SPLC commissioning mode active

Heidenhain · TNC CNC Controllers

¿Qué significa 231-A003 ?

This error indicates that the Safety PLC (SPLC) commissioning mode is still active. This happens when the CRC check of the SPLC program is deactivated (machine parameter CfgSafety --> commissioning is set), which is typically done during machine setup but must be deactivated before machine delivery for safe operation.

Causas comunes

  • CRC check of the SPLC program is deactivated (machine parameter CfgSafety --> commissioning is set).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Deactivate the commissioning mode by resetting the 'commissioning' setting in the machine parameter CfgSafety.

  2. 2

    Verify that the CRC check of the SPLC program is enabled after deactivating commissioning mode.

  3. 3

    Confirm that the machine is ready for production operation with all safety features active.