416
No communication possible between power stage set and control system.
Fronius · Primo GEN24 Operating Instructions
¿Qué significa 416 ?
This code indicates a failure in communication between the inverter's power stage set and its control system. This prevents normal operation, but the inverter will automatically attempt to re-establish communication and resume feeding energy into the grid.
Causas comunes
- Faulty communication link (e.g., ribbon cable, bus connection) between the power and control boards.
- Malfunction of communication transceivers on either the power stage or control system.
- Electromagnetic interference disrupting the communication channel.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
If the status code is displayed continuously, notify a Fronius-trained service engineer for diagnosis.
- 2
Perform an AC reset by cycling the automatic circuit breaker to restart the inverter's internal communication.
- 3
Inspect internal communication cables for damage or loose connections.