Traduciendo...
103

AC voltage too low

Fronius · Primo GEN24 Operating Instructions

¿Qué significa 103 ?

This code indicates that the AC voltage supplied by the public grid is too low, preventing the inverter from feeding energy into the grid. The inverter disconnects but will attempt to reconnect once grid conditions improve.

Causas comunes

  • AC grid voltage drops below the permissible lower limit for the inverter's operation.
  • Voltage sags on the public grid due to high loads or faults.
  • Potential issues with the grid connection integrity or undersized AC cabling.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect the AC grid connections for any loose or damaged wiring.

  2. 2

    Measure the AC voltage on the inverter connection sockets to verify it meets the required 220/230 V (+10% / -5%) or 380/400 V (+10% / -5%) range.

  3. 3

    If this status code keeps recurring, contact your system fitter or grid operator to investigate grid quality.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Fronius Primo GEN24 Operating Instructions
Fronius 103 AC voltage too low: Información de servicio | ErrorLib