Traduciendo...
102

AC voltage too high

Fronius · Primo GEN24 Operating Instructions

¿Qué significa 102 ?

This code indicates that the AC voltage supplied by the public grid is excessively high. The inverter will temporarily disconnect from the grid but will automatically attempt to resume energy feeding once grid conditions return to the permissible range.

Causas comunes

  • AC grid voltage exceeds the permissible upper limit for the inverter's operation.
  • Transient overvoltage events on the public grid.
  • Potential issue with the grid connection itself.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect the AC grid connections for any loose or damaged wiring.

  2. 2

    Measure the AC voltage on the inverter connection sockets to verify it is within 220/230 V (+10% / -5%) or 380/400 V (+10% / -5%).

  3. 3

    If this status code keeps recurring, contact your system fitter or grid operator to investigate grid quality.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Fronius Primo GEN24 Operating Instructions