Bosch Rexroth IndraDrive Troubleshooting
16 Fehlercodes dokumentiert
PLC - Warning no. 1
The drive-integrated PLC generates this warning (E2011 .. E2014) in conjunction with technology functions within the PLC program. The specific cause and remedy depend on the active PLC project or Rexroth technology function.
PLC - Warning no. 2
The drive-integrated PLC generates this warning (E2011 .. E2014) in conjunction with technology functions within the PLC program. The specific cause and remedy depend on the active PLC project or Rexroth technology function.
PLC - Warning no. 3
The drive-integrated PLC generates this warning (E2011 .. E2014) in conjunction with technology functions within the PLC program. The specific cause and remedy depend on the active PLC project or Rexroth technology function.
Dynamization failed
This warning occurs in normal operation when safety technology is activated. It indicates that no dynamization pulse occurred at the dynamization input within the time P-0-3223, Time interval for dynamization of safety function selection, or the pulse width deviates from P-0-3224, Duration of dynamization pulse of safety function selection. If a safety function is selected, this condition would trigger F3134 Dynamization time interval incorrect or F3135 Dynamization pulse width incorrect errors.
Plausibility error of safety parameters
This warning occurs in normal operation when safety technology is activated. It indicates a comparison showed that channel 1 and channel 2 are not operating with the same safety parameters. If a safety function is selected, this condition would trigger the F3140 Plausibility error of safety parameters error.
Error when initializing digital inputs/outputs
An error occurred during the drive's initial startup sequence, specifically during the initialization of the digital inputs and outputs. This indicates a configuration conflict or issue with the I/O parameters.
PLC - Error nr. 1
This error message is generated by the integrated PLC (optional expansion package "drive PLC") within the drive, typically in conjunction with technology functions. The specific cause depends on the active PLC project or technology function.
PLC - Error nr. 2
This error message is generated by the integrated PLC (optional expansion package "drive PLC") within the drive, typically in conjunction with technology functions. The specific cause depends on the active PLC project or technology function.
PLC - Error nr. 3
This error message is generated by the integrated PLC (optional expansion package "drive PLC") within the drive, typically in conjunction with technology functions. The specific cause depends on the active PLC project or technology function.
Softstart fault power supply unit
During the soft start process, which involves loading the DC bus capacitance, the DC bus voltage curve is monitored. Significant deviations from the expected curve suggest a defect in the power section of the HMV01 supply unit. This fault indicates a problem specifically during the initial power-up sequence.
Overvoltage in power section
This error occurs if the warning E8025 Overvoltage in power section persists for more than 2 seconds. When triggered, the drive's power is switched off. It indicates an excessive voltage condition within the power section of the HMV01 supply unit.
Error supply shutdown
This error is triggered when a second supply unit or converter connected in parallel signals a supply error. It indicates an issue in a linked power supply component, leading to a shutdown of the main supply.
Overcurrent in mains-side power section
The current in the power transistor bridge has exceeded the maximum allowed device peak current. This results in the immediate de-energization of the drive, causing the motor to coast to a stop. The power supply is switched off due to this excessive current condition.
Invalid device code
This error indicates that an invalid device code has been detected within the HMV01 supply unit. This typically suggests an internal hardware malfunction or incorrect identification of the device itself.
Timeout during loading process
During the initial loading of the DC bus (soft start) before switching on the power supply, the expected DC bus voltage could not be reached within the allotted time window. This indicates a problem with the DC bus charging circuit or excessive load.
Connection error mains choke
After the power supply had been switched on, a wiring error of the mains choke, such as an incorrect phase sequence of the mains phases, was detected. This fault indicates an improper connection of the mains choke.