E8030

Negative position limit exceeded

Bosch Rexroth · IndraDrive C Drive Controllers

Was bedeutet E8030 ?

The actual or commanded position has exceeded the configured negative software travel limit. This can lead to the machine reaching its mechanical hard stop or unexpected motion.

Häufige Ursachen

  • Programmed motion or jog command attempts to move beyond the negative software travel limit.
  • Incorrectly set negative software limit parameter.
  • Loss of position feedback or incorrect encoder scaling, leading to misinterpretation of actual position.
  • Mechanical overtravel due to inertia or incorrect braking.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the negative software travel limit parameter in the drive controller and ensure it is set correctly and safely for the application.

  2. 2

    Check the commanded position values in the motion program to ensure they do not exceed the negative travel limit.

  3. 3

    Inspect the position feedback system for encoder accuracy and scaling parameters.

  4. 4

    Manually jog the axis to a safe position within the valid travel range.