Übersetzen...
E8029

Positive position limit exceeded

Bosch Rexroth · IndraDrive C Drive Controllers

Was bedeutet E8029 ?

The actual or commanded position has exceeded the configured positive software travel limit. This can lead to the machine reaching its mechanical hard stop or unexpected motion.

Häufige Ursachen

  • Programmed motion or jog command attempts to move beyond the positive software travel limit.
  • Incorrectly set positive software limit parameter.
  • Loss of position feedback or incorrect encoder scaling, leading to misinterpretation of actual position.
  • Mechanical overtravel due to inertia or incorrect braking.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the positive software travel limit parameter in the drive controller and ensure it is set correctly and safely for the application.

  2. 2

    Check the commanded position values in the motion program to ensure they do not exceed the positive travel limit.

  3. 3

    Inspect the position feedback system for encoder accuracy and scaling parameters.

  4. 4

    Manually jog the axis to a safe position within the valid travel range.

Alle Codes in diesem Handbuch durchsuchen (66)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Bosch Rexroth IndraDrive C Drive Controllers