E2802

HW control of braking resistor

Bosch Rexroth · IndraDrive C Drive Controllers

Was bedeutet E2802 ?

This warning indicates an issue with the hardware control circuit for the braking resistor. This could prevent the braking resistor from dissipating regenerated energy, potentially leading to overvoltage faults.

Häufige Ursachen

  • Fault in the braking resistor control circuitry within the drive.
  • External braking resistor or its wiring is open-circuited or damaged.
  • Malfunction of the internal braking transistor or associated components.
  • Incorrect parameterization of the braking resistor characteristics.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect the external braking resistor and its connections for damage, loose wiring, or open circuits. Measure its resistance to confirm it's within specifications.

  2. 2

    Verify that the braking resistor cable is correctly wired and securely terminated to the drive.

  3. 3

    Check the drive's internal diagnostics for specific sub-errors related to the braking circuit.

  4. 4

    If possible, test the braking transistor using drive diagnostics or by observing DC bus voltage during regeneration with a known good resistor.