E2056

Torque limit = 0

Bosch Rexroth · IndraDrive C Drive Controllers

Was bedeutet E2056 ?

The torque limit parameter is set to zero, preventing the motor from generating any torque. This causes the drive to be unable to move or hold position.

Häufige Ursachen

  • Torque limit parameter was intentionally or accidentally set to 0.
  • External PLC or HMI command setting the torque limit to 0.
  • System logic error preventing the torque limit value from being set above 0.
  • Emergency stop or safety function that reduces the torque limit to zero.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the torque limit parameter in the drive controller and ensure it is set to a non-zero, appropriate value for the application.

  2. 2

    Check the machine's HMI or control program for any active torque limit settings that might be forced to 0.

  3. 3

    Trace the logic controlling the torque limit to ensure no unexpected conditions are setting it to zero.

  4. 4

    Check if any active safety functions or emergency stops are causing the torque limit to be set to zero. Resolve the safety condition if present.