F016

Main overvoltage

Schindler · Easy Altivar ATV310 Drive

What does F016 mean?

This ATV310 fault occurs when the incoming line voltage supplied to the drive is excessively high. This can be triggered at power-on (10% over maximum acceptable voltage) or when idle (20% over maximal line supply), or by a disturbed mains supply.

Common Causes

  • Line voltage too high at drive power on (exceeding 10% over the maximum acceptable voltage level)
  • Line voltage too high when powered with no run command (exceeding 20% over maximal line supply)
  • Disturbed mains supply with transient overvoltages

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Turn off the ATV310 drive and verify the incoming line voltage using a multimeter or power quality analyzer.

  2. 2

    Adjust the line voltage from the source to ensure it is within the drive's specified nominal voltage range and tolerances.

  3. 3

    After the line voltage returns to nominal (within tolerance), power on the drive.

  4. 4

    If intermittent F016 codes appear, set parameter 205 (R1 assignment) to 01 and connect the R1 relay output to upstream protection to avoid drive overvoltage.

Browse all codes in this manual (37)
Verified technical data. Last updated: March 2026