F033
AI1 current loss
Schindler · Easy Altivar ATV310 Drive
What does F033 mean?
For the ATV310 drive, this fault is detected if Analog input AI1 is configured for current (parameter 204.1 > 3 mA) and the actual analog input current falls below 2 mA. This indicates a loss of signal from the connected sensor or a wiring integrity issue at the input.
Common Causes
- Analog input AI1 is configured as current (parameter 204.1 is greater than 3 mA)
- Analog input current on AI1 is lower than 2 mA
- Poor or loose terminal connection at AI1
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify wiring and terminal connections for analog input AI1 on the drive.
- 2
Measure the current signal at analog input AI1 terminals to ensure it is above 2 mA.
- 3
Check parameter 204.1 (AI1 current scaling parameter) to confirm it is configured correctly and set greater than 3 mA.
- 4
Inspect the sensor providing the AI1 signal for proper operation and adequate power supply.
Verified technical data. Last updated: March 2026
Related Faults
Source: Schindler Easy Altivar ATV310 Drive