Vacon · NX All-in-One Application

Hva betyr 10 ?

An input line phase is missing, indicating a loss of one or more phases in the AC supply to the drive. This could be due to an open circuit in the supply cabling, a blown fuse, or a power distribution issue. Operating with a missing phase can damage the drive's input rectifier.

Vanlige årsaker

  • Input AC power phase is missing or unbalanced.
  • Faulty input power rectifier or smoothing circuit.
  • Loose connection on the AC input terminals.
  • External power source fluctuation.
  • Overload on the input stages.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the phase-to-phase and phase-to-neutral supply voltages at the drive's input terminals — verify all phases are present and balanced.

  2. 2

    Inspect all input fuses for continuity and ensure they are of the correct type and rating.

  3. 3

    Physically check the supply cables connecting to the drive for any signs of damage, loose connections, or disconnections at the terminal block.

Se alle koder i denne manualen (42)
Verifisert teknisk data. Sist oppdatert: March 2026