F43
RS485 timeout
SEW Eurodrive · MOVITRAC 07B System
Hva betyr F43 ?
Communication over the RS485 interface between the inverter and a PC, or to the FSE24B module, has been interrupted. This fault does not lock the drive and clears automatically once communication is reestablished, indicating a transient or connection issue.
Vanlige årsaker
- Physical connection interruption between the inverter and a PC via RS485
- Interruption in communication link to the FSE24B interface module
- Loss of voltage supply to the FSE24B communication module
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the physical RS485 connection cable between the inverter and the PC.
- 2
Check the voltage supply to the FSE24B communication interface module.
- 3
Inspect parameter P808 settings related to auxiliary voltage output, which might affect FSE24B power.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: SEW Eurodrive MOVITRAC 07B System