F116

Error application module

SEW Eurodrive · MOVITRAC 07B System

Hva betyr F116 ?

A general error originating from an application module, indicating a problem in the drive's specialized control functions. This fault has several specific sub-errors that further define the nature of the issue, such as encoder problems or limit switch activations.

Vanlige årsaker

  • Suberror 14: Encoder error, indicating an issue with the motor's feedback device.
  • Suberror 29: A limit switch has been reached, restricting motion beyond defined boundaries.
  • Suberror 42: Lag error, meaning the actual position/speed deviates significantly from the commanded setpoint.
  • Suberror 78: A software limit switch has been reached, enforced by configured parameters.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    For Lag Error (Suberror 42), adjust speed monitoring thresholds by changing parameters P500 / P502 (speed monitoring 1/2) and P501 / P503 (delay time 1/2).