82
Output phases interrupted
SEW Eurodrive · MOVIMOT MM..D With AC Motor DRS
Hva betyr 82 ?
Two or all output phases to the motor are interrupted, or there is a significant mismatch between the motor and inverter power ratings, preventing the motor from receiving power correctly.
Vanlige årsaker
- Two or all output phases to the motor are interrupted
- Rated motor power is too small in relation to the rated inverter power
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the connection between the MOVIMOT® inverter and motor for any interrupted phases
- 2
Verify the rated motor power is appropriately matched with the rated inverter power
- 3
Reset the error by switching off the DC 24 V supply voltage
- 4
Reset the error via the control system or dedicated reset function
Verifisert teknisk data. Sist oppdatert: March 2026