F917
REVERSE ARM. V. FEEDBACK
Otis · DSD 412 Elevator System
Hva betyr F917 ?
This fault is detected by the PCU Diagnostics function (Function #998) and indicates that the Armature Feedback wires are either reversed or not connected at all.
Vanlige årsaker
- Armature Feedback wires are incorrectly connected in reverse polarity.
- Armature Feedback wires are not connected to the drive.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Remove power from the drive.
- 2
Inspect the Armature Feedback wires and reverse them if connected incorrectly.
- 3
Verify that the Armature Feedback wires are securely connected.
- 4
Repeat the PCU Diagnostics function to confirm the issue is resolved.