SERIAL COMMUNICATION FAULT

Otis · DSD 412 Elevator System

Hva betyr 117/118 ?

Code 117 indicates serial communication did not start within 10 seconds after drive reset or power-up. Code 118 indicates a valid serial communication message was not received for more than 150 ms.

Vanlige årsaker

  • Host not connected or not sending valid messages.
  • Electrical grounding noise interference.
  • Parameter #110 set to selection 3 when serial communication is not being used.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Ensure the host is connected and sending valid messages.

  2. 2

    Identify and correct electrical grounding noise interference problems.

  3. 3

    If serial communication is not being used, verify parameter #110 is NOT set to selection 3.