402
LOOP CONTACTOR FAULT
Otis · DSD 412 Elevator System
Hva betyr 402 ?
The DSD 412 drive detects that the Loop Contactor auxiliary contact failed to pick up or drop out within the expected timeframe. This behavior is governed by the setting of parameter #102.
Vanlige årsaker
- Defective Loop Contactor Auxiliary contact, failing to provide proper feedback.
- Defective main Contactor, potentially due to an open coil or mechanical binding.
- Defective Pilot Relay LPR.
- Electrical interference originating from other elevator relay contact circuits.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check for proper feedback from the Loop Contactor Auxiliary contact at terminal TB1-7.
- 2
Inspect the main Contactor for an open coil or any signs of mechanical binding.
- 3
Check the Pilot Relay LPR for proper operation.
- 4
Investigate and mitigate any interference from other elevator relay contact circuits.
Verifisert teknisk data. Sist oppdatert: March 2026