925
FIELD SENSE FAULT
Otis · DSD 412 Elevator System
Hva betyr 925 ?
The field bridge rating is determined by reading a sense resistor on the Field Interface board selected by SW1. If the resistance value is not recognized, a Field Sense Fault is declared, indicating a hardware fault. This fault requires a DSD power down.
Vanlige årsaker
- Hardware fault on the Field Interface PCB.
- Hardware fault on the Drive Control PCB.
- Fault in interconnecting cables or hardware.
- J13 not seated properly.
- Defective cable.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check that J13 is seated properly.
- 2
Inspect the cable for defects.
- 3
Verify the Field Interface board selection via SW1 and the sense resistor value.
- 4
Replace the Field Interface PCB if faulty.
- 5
Replace the Drive Control PCB if faulty.