911

SHORTED SCRS/DOUBLER FAULT

Otis · DSD 412 Elevator System

Hva betyr 911 ?

One of the SCR/Doubler packs has a short circuit between the SCRs. This condition is checked only upon request through the PCU #998 Diagnostics CDU function. The optional handheld PCDU can identify which specific SCR pair is faulty. This fault requires a DSD Power Down.

Vanlige årsaker

  • Short circuit between SCRs in an SCR/Doubler pack.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Use the PCU #998 Diagnostics CDU function to identify the shorted SCR pair.

  2. 2

    Replace the faulty SCR/Doubler pack.