908
OVER TEMPERATURE FAULT
Otis · DSD 412 Elevator System
Hva betyr 908 ?
The calculated SCR junction temperature is above 125 degrees Centigrade. This is derived from the thermistor heat sink measurement combined with the heating effects of measured armature output current on the SCRs. This fault will not shut down the drive.
Vanlige årsaker
- Ambient temperature too high.
- Clogged air filter in cabinet.
- Clogged heat sinks.
- Cooling fan failure.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check ambient temperature for high levels and address the underlying cause.
- 2
Clean or replace the air filter in the cabinet.
- 3
Clean the heatsink fins.
- 4
Replace defective cooling fan(s) in the power cube.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Otis DSD 412 Elevator System