Armature Circuit Open (Loop Confirm)
Otis · DSD 412 DC Elevator Drive
Hva betyr F901 ?
This fault is triggered if the motor armature circuit is not closed before the "Loop Confirm" signal asserts, preventing the drive from establishing a closed current path to the motor. It indicates a disconnection that inhibits motor operation and often occurs during the drive's startup sequence.
Vanlige årsaker
- Disconnection or damage in the motor armature power cabling between the drive and the motor.
- Failure of the main armature contactor to close properly, leaving the circuit open.
- Issues with the "Loop Confirm" input signaling closure prematurely when the armature path is still open.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
De-energize the drive and visually inspect all motor armature power connections for looseness or damage.
- 2
Perform a continuity check on the motor armature power cables and through the main armature contactor's power contacts.
- 3
Confirm that the "Loop Confirm" input signal accurately reflects the actual closed state of the armature circuit.
- 4
Verify the motor's armature winding resistance against manufacturer specifications.