Oversetter...
117/118
SERIAL COMMUNICATION FAULT
Otis · DSD 412 DC Elevator Drive
Hva betyr 117/118 ?
Fault 117 occurs if serial communication does not start within 20 seconds after drive reset or power up. Fault 118 occurs if a valid serial communication message is not received for more than 150 milliseconds.
Vanlige årsaker
- Host system is not connected or not sending valid messages.
- Electrical grounding noise interference.
- Serial communication is not being used, but parameter #110 is set to selection 3.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Ensure that the host is connected and sending valid messages.
- 2
Look for and correct electrical grounding noise interference problems.
- 3
If serial communication is not being used, verify that parameter #110 is NOT set to selection 3.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Otis DSD 412 DC Elevator Drive