THERMISTOR FAULT

Otis · DSD 412 DC Elevator Drive

Hva betyr 907 ?

The thermistor used for temperature sensing is detected as either open or shorted. This fault can also occur if the ambient machine room temperature is below 0°C, causing the detected resistance to be abnormally high. On larger drives, an open thermostat will also trigger this fault. This fault will not shut down the drive.

Vanlige årsaker

  • An open circuit in the thermistor or its wiring.
  • A short circuit in the thermistor or its wiring.
  • Ambient machine room temperature falling below 0°C, leading to excessively high thermistor resistance readings.
  • An open thermostat on larger drive models.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the thermistor and its wiring for open or short circuits; it should measure between 2K – 10K ohms at 20C room temperature.

  2. 2

    Verify that the machine room ambient temperature is above 0°C.

  3. 3

    On larger drives, inspect the thermostat for an open circuit.