FIELD LOSS FAULT
Otis · DSD 412 DC Elevator Drive
Hva betyr 905 ?
The field current feedback has dropped below 80% of the expected current under specific operating conditions: during Field Weakening Mode (top speed, parameter #49), Full Field Mode (acceleration or deceleration, parameter #50), or Standing Field Mode (not running, parameter #53). This fault will shut down the drive.
Vanlige årsaker
- Open circuit failure in the motor field winding or its associated wiring.
- Hardware failure within the motor field control circuitry.
- Loss of power or incorrect phasing supplied to the Field Rectifier.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Inspect the motor field winding and wiring for any open circuits.
- 2
Check the power supply and phasing to the Field Rectifier for correct operation.
- 3
Test the motor field control circuitry for any hardware malfunctions.
- 4
Review parameters #49, #50, and #53 to ensure they accurately reflect the expected field current values for the respective operating modes.