903

LINE SYNCRONIZATION FAULT

Otis · DSD 412 DC Elevator Drive

Hva betyr 903 ?

The Phase Locked Loop (PLL) has lost synchronization with the 3-phase AC input power supply. This sets the Severe Fault flag, forces the DSD 412 current reference to zero, and shuts down the drive. This fault is generally caused by AC input power problems, is often self-correcting, and may occur in conjunction with an F904 fault. A CPU Reset is required.

Vanlige årsaker

  • Problems with the 3-phase AC input power quality, such as voltage fluctuations or frequency deviations.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Monitor the 3-phase AC input power supply for stability, voltage, and frequency variations.

  2. 2

    Perform a CPU reset on the Drive Control PCB once the AC input power issues have been resolved.

Se alle koder i denne manualen (48)
Verifisert teknisk data. Sist oppdatert: March 2026